IVS1(F)

IVS voltage transformers are designed for transmitting information signals to measuring devices, protection, signaling and control devices.

Transformers shall be installed in a dry location, where the environment is non-explosive, free of dust, reactive gases and vapors in concentrations able to destroy metal coatings and insulation.

The operating temperature range is from -45 ° C to +50 ° C.

The height of the installation above sea level - not more than 1000 m.

U Climatic performance, 2 category  according to GOST 15150.

Transformers comply with DSTU EN 61869-1:2017, DSTU EN 61869-3:2017, GOST 1983-2015.

Compare

IVS voltage transformers are designed for transmitting information signals to measuring devices, protection, signaling and control devices.

Transformers shall be installed in a dry location, where the environment is non-explosive, free of dust, reactive gases and vapors in concentrations able to destroy metal coatings and insulation.

The operating temperature range is from -45 ° C to +50 ° C.

The height of the installation above sea level - not more than 1000 m.

U Climatic performance, 2 category  according to GOST 15150.

Transformers comply with DSTU EN 61869-1:2017, DSTU EN 61869-3:2017, GOST 1983-2015.

  • Parameter name Parameter value
  • Highest voltage for equipment, Um, [kV] 3,6; 7,2; 12
  • Number of secondary windings 1, 2, 3
  • Power-frequency test voltage, [kV] 10, 20, 28
  • Rated voltage of primary winding, Un, [kV] 3,0/√3; 3,3/√3; 3,6/√3; 6/√3; 6,3/√3; 6,6/√3; 10/√3; 10,5/√3; 11/√3
  • Rated voltage of main secondary winding, [V] 100/√3; 110/√3; 120/√3
  • Rated voltage of residual secondary winding, [V] 100; 110; 120; 100/√3; 110/√3; 120/√3; 100/3; 110/3; 120/3
  • Rated burden of main secondary winding in accuracy class, [VA/cl] 25/0,2; 50/0,5; 100/1; 150/3
  • Rated burden of residual secondary winding in accuracy class, [VA/cl] 150/3P; 150/6P
  • Thermal limiting output, [VA] 400; 500; 630
Recommended articles
What happens at solar power plants (SPP)?
<p>Beontop company has been producing instrument voltage transformers (VT) for eight years. Currently, about 10 thousand transformers of our production are in operation. From time to time, we receive messages about the failure of the VT.</p> <p>Up to 65% of failure cases occur at solar power plants (SPP), despite the fact that the percentage of VTs operated at SPP does not exceed 5-10% of the total.</p>